Mine water treatment in Chile: discharge rules, acid drainage and copper process water

Home Mine water treatment in Chile: discharge rules, acid drainage and copper process water

In Chile, the target for mine water treatment is set less by the technology than by where the water ends up. A discharge to a river is judged against Table 1 of Supreme Decree 90 of 2000 (DS 90), which caps sulfate at 1,000 mg/L and chloride at 400 mg/L. A discharge to the sea outside the coastal protection zone is judged against Table 5, which sets no limit for either. Infiltration to an aquifer falls under a separate decree, and water that stays inside the process has no emission standard at all, only the conditions of the project’s environmental approval.

That is why two copper mines with similar acid drainage can need very different treatment plants. This page sets out the Chilean rules that fix the target, the three kinds of mine water they apply to, and the treatment steps that usually follow. Brine Consulting is an independent industrial water advisory firm in Amsterdam with no treatment equipment to sell, which lets us start where a Chilean mine should start: with the discharge route and the limit it brings, before any plant is quoted. We take on Chilean sites remotely or through a defined engagement.

Three kinds of mine water, three different problems

Acid rock drainage. Sulfide minerals such as pyrite oxidise when water and air reach them in pits, waste dumps, leach residues and tailings. The result is acidic water carrying copper, aluminium, iron, arsenic and sulfate. In the Andes, mineralised ground can also shape the background water. Yerba Loca Creek, in the foothills above Santiago, runs over a large copper porphyry deposit that the study’s authors say has long influenced its water quality; it was measured at pH 3.75 with 4.8 to 6.5 mg/L of copper (Rodríguez et al., Water, 2018). Background water like this matters for the discharge limit, as explained below.

Copper process and tailings water. Concentrators reuse most of their water. Cochilco, the Chilean Copper Commission, put recovered and recirculated water at 72.5% of all the water used by the country’s copper mines in 2025, in figures released in October 2026 (as reported by Guía Minera, October 2026). What is not recovered, and any bleed stream, carries reagents, molybdenum, sulfate and, more and more often, sea salt. The same figures show about 2.4 m³/s of seawater used without desalination in 2025. A concentrator that runs on raw or partly desalinated seawater produces process water far saltier than any freshwater discharge limit allows.

Dewatering water. Pits and underground workings intercept groundwater. Since the 2022 reform of the Water Code (Law 21.435), a mining concession holder who finds water in exploration or mining works must report it to the Dirección General de Aguas (DGA) within 90 calendar days, with its location, flow, the activities that justify its use and any surplus. The DGA checks that the use does not endanger aquifers or third-party rights, and can limit it (summary by the law firm CMS, April 2022). The DGA set out a restrictive reading of the rule in Exempt Resolution 2600 of October 2022 (summary by the law firm Prieto). Dewatering water that is not needed has to go somewhere, and that route brings it back under the discharge rules.

The discharge route sets the treatment target

The table compares the limits that usually decide a copper mine’s treatment design, taken from DS 90 as published on 7 March 2001 (DS 90 text, FAOLEX copy). All values are maximum concentrations in mg/L.

Where the water goes Rule Sulfate Chloride Arsenic Copper Molybdenum
River, no dilution credit DS 90, Table 1 1,000 400 0.5 1 1
Sea, inside the coastal protection zone (ZPL) DS 90, Table 4 Not limited Not limited 0.2 1 0.1
Sea, outside the ZPL DS 90, Table 5 Not limited Not limited 0.5 3 0.5

Four points follow from those tables.

  1. Sulfate and chloride decide whether a river discharge is affordable. Seawater itself contains about 2,680 mg/kg of sulfate and 19,160 mg/kg of chloride (Britannica, seawater composition at salinity 34.7). That is roughly 2.7 times the Table 1 sulfate limit and 48 times the chloride limit. Water that has passed through a seawater-fed concentrator cannot reach a river without being desalted.

  2. At sea, the burden shifts to metals. The molybdenum limit inside the coastal protection zone is 0.1 mg/L, ten times tighter than for a river. For a copper-molybdenum circuit, an outfall close to shore can be the harder target, not the easier one. A sea outfall also needs its own permits and a pipeline to the coast.

  3. Natural content can move the limit. Where the natural concentration of a contaminant in the receiving water is above the table value, DS 90 sets the discharge limit equal to that natural content. The same applies to the intake water’s content when intake and discharge are in the same water body. The DGA determines natural content, or DIRECTEMAR, the maritime authority, for marine waters, and the discharger must report it to rely on it (DS 90, sections 3.2, 3.3, 4.1.3 and 5.2). In Andean basins with acidic, metal-rich background water, establishing this with data before sizing a plant can relax the parameter that would otherwise drive the design.

  4. Tailings systems are outside the tables. DS 90 does not treat artificial water bodies that store or treat tailings as receiving bodies, and the groundwater decree excludes tailings deposits from its scope. Water inside the tailings system is governed by the project’s environmental approval and its closure obligations, not by the emission tables.

Discharges that infiltrate to an aquifer fall under Supreme Decree 46 of 2002, which caps sulfate at 250 mg/L where aquifer vulnerability is medium and 500 mg/L where it is low (DS 46/2002, Ministry of the Environment copy).

Why does lime treatment alone fall short on sulfate?

Lime neutralisation, often run as a high-density sludge process, is the workhorse for acid drainage. It raises pH and precipitates most dissolved metals as hydroxides. It does not take sulfate much below the solubility of gypsum. In a pilot reported by Tetra Tech engineers, lime pre-treatment lowered sulfate from 1,900 to 1,400 mg/L, and the authors concluded that gypsum precipitation alone could not meet a 600 mg/L limit. The nanofiltration permeate in the same pilot averaged 2.3 mg/L (Liang, Tamburini and Johns, IMWA 2015). Engineers at Amec Foster Wheeler add that lime effluent is usually still supersaturated with gypsum at discharge, because gypsum precipitates slowly (Aubé and Lee, IMWA 2015).

In Chilean terms, that gives three typical situations:

  • Sea outfall outside the coastal protection zone. Lime precipitation followed by polishing for the metals that do not drop out at the same pH, such as molybdenum and arsenic, may be enough, because sulfate and chloride are not limited. The environmental approval can still add conditions.

  • River discharge of sulfate-rich drainage. On the pilot data above, we would not count on lime alone to hold 1,000 mg/L of sulfate reliably. A second step is needed: nanofiltration or reverse osmosis, ettringite precipitation (below 200 mg/L in the Tetra Tech bench tests) or ion exchange. Each step creates a concentrate or sludge that also needs a home.

  • Saline process water heading to a river or an aquifer. Desalting is unavoidable, and the reject becomes the real design problem: it has to go to the sea, to evaporation or to a zero liquid discharge train. Our guide to evaluating the disposal endpoint first explains why that question comes before technology selection, and our heavy metal removal guide compares the polishing options.

What drives the cost. Published Chilean treatment costs are scarce, so we give drivers rather than prices. In our view, most of the cost gap between these three situations comes from two choices: whether a desalting step is needed at all, and where its concentrate or sludge ends up. Closure, covered below, then decides for how many years the plant has to run.

The DS 90 revision: approved, then withdrawn

The decree replacing DS 90 got a favourable opinion from Chile’s Council of Ministers for Sustainability and Climate Change in January 2026 (CPI, citing La Discusión, August 2026) and was sent to the Comptroller General (Contraloría) for legal review. On 12 March 2026 the incoming government withdrew it, together with 42 other environment decrees (Chile Sustentable, June 2026; La Tercera). By October 2026 only 9 of the 43 had been resubmitted (El Desconcierto, October 2026). The text approved by the council (MMA, February 2026) still shows where the rules were heading. It would:

  • Repeal DS 90 on publication, while existing DS 90 limits and resolutions stay in force until the new limits apply.

  • Keep the limits in the table above for sulfate, chloride, arsenic, copper and molybdenum, in rivers and at sea.

  • Require at least one acute toxicity test a year for sources discharging more than 300 m³/day to continental surface waters.

  • Give existing sources phased compliance deadlines.

We found no report of its resubmission or publication in the Diario Oficial as of 4 November 2026. DS 90/2000 remains in force. Our advice for a plant designed now is to meet DS 90 and, for a river discharge above 300 m³/day, leave room for toxicity testing in case the revision returns in a similar form.

Closure turns water treatment into a long-term question

Chile’s mine closure law, Law 20.551, requires closure plans, and the national mining service Sernageomin treats chemical stability as part of them: controlling acid-generating reactions by keeping water away from reactive material. Its guidance stresses selective placement of waste, separate handling of contact and non-contact water, covers, and passive or active treatment (Sernageomin presentation of its chemical stability guide, August 2015). A treatment plant chosen only for today’s flows can become a liability if drainage continues after production stops, so the closure horizon belongs in the design basis.

What to have ready before choosing a treatment train

  1. The route and the rule: which DS 90 table, or which DS 46 vulnerability class, applies, plus the conditions in the project’s environmental approval (RCA).

  2. Background data for the receiving water, if you may rely on natural content.

  3. Flows by source: contact water, dewatering, process bleed, with how they vary over the year.

  4. A complete ion analysis, including sulfate, chloride, calcium, magnesium, molybdenum and arsenic, checked for internal consistency. Our free Water Analysis Validator calculates the charge-balance error and compares the ion sum with reported TDS.

  5. The seawater share of process water now and in the mine plan. Our page on desalination for mining in Chile covers the supply side.

  6. Where residues go: lime sludge, gypsum and membrane concentrate, and whether the tailings facility can take them. The brine mass balance calculator and MLD vs ZLD screener help size that question early.

  7. For dewatering water, the status of the report to the DGA.

What an independent review covers on a Chilean mine water project

Our work on Chilean mine water sits before and between supplier offers: checking which DS 90 table or DS 46 class the design basis is written against, testing whether natural content data could move a limit, screening sulfate removal routes before suppliers are invited, putting vendor offers on one baseline, and settling early where concentrate and sludge will go. See our water treatment and ZLD consulting and advisory and due diligence services, our overview of zero liquid discharge for mining, our Chile page and our page on lithium brine processing in Chile.

Bring the discharge route you are considering and a recent ion analysis to a scoping call, and we can talk through which limit is likely to drive the plant and what data is still missing. If you prefer to start in writing, send us your project details.

Written by the Brine Consulting advisory team. The Brine Consulting advisory practice includes Osis G. Kalache, P.Eng., Senior Consultant in wastewater process engineering and optimization with more than 17 years of experience in industrial and conventional wastewater treatment, and Dimitra Aravani, External Advisor on industrial wastewater and water reuse with more than a decade of experience, including troubleshooting, system audits and technology assessment. Meet our experts.

Questions about your site's water or brine?